Product Transition Guide
Appendix 2- Parameter Differences
GPD515/G5 Parameters
G7 Parameters
Parameter
No.
Name
(DigitalOperator Display)
Setting or Selection
Parameter
No.
Name
(Digital Operator Display)
Remarks on
Setting or Selection
L6-01
Overtorque
Detection Selection 1
0: Disabled
1: @SpdAgree - Alm
2: At RUN - Alarm
3: @SpdAgree - Flt
4:At RUN - Fault
L6-01
Torque Detection
Selection 1
Additional selections:
5: UL3 at SpeedAgree - Alarm Undertorque
Detec tion is only active during Speed Agree
and operation continues after detection.
6: UL3 at RUN - Alarm Undertorque
Detection is always active and operation
continues after detection.
7: UL3 at Speed Agree - Fault Undertorque
Detection only active during Speed Agree
and drive output will shut down on an OL3
fault.
8: UL3 at RUN - Fault Undertorque
Detection is always active and drive output
will shut down on an OL3 fault.
L6-04
Overtorque
Detection Selection 2
0: Disabled
1: @SpdAgree - Alm
Detected during speed agree
only.
2: At RUN - Alarm
Overtorque detection during
running.
3: @SpdAgree - Flt
Detected during the speed
agree only.
4: At RUN - Fault
Detected during running, and
the inverter trips on OL4.
L6-04
Torque Detection
Selection 2
Additional selections:
5: UL4 at SpeedAgree - Alarm Undertorque
Detec tion is only active during Speed Agree
and opera tion continues after detection.
6: UL4 at RUN - Alarm Undertorque
Detection is always active and operation
continues after detection.
7: UL4 at Speed Agree - Fault Undertorque
Detection only active during Speed Agree
and drive out put will shut down on an OL4
fault.
8: UL4 at RUN - Fault Undertorque
Detection is always active and drive output
will shut down on an OL4 fault.
L8-07
Output phase loss
protection
0: Disabled
1: Enabled
L8-07
Output phase loss
protection
Additional selections
2: 2/3 phase loss protection
L8-10
Short-circuit
Protection Selection
0:Disabled
1: Enabled
L8-09
Output Ground Fault
Detection Selection
Changed parameter number
—
—
—
L8-10
Heatsink Cooling Fan
Operation Selection
New parameter
0: Fan On-Run Mode
1: Fan Always On
—
—
—
L8-11
Heatsink Cooling Fan
Operation Delay Time
New parameter
—
—
—
L8-12
Ambient Temperature
Setting
New parameter