Product Transition Guide
GPD515/G5 to G7
GPD515/G5 Parameters
G7 Parameters
Parameter
No.
Name
(DigitalOperator Display)
Setting or Selection
Parameter
No.
Name
(Digital Operator Display)
Remarks on
Setting or Selection
—
—
—
H6-01
Pulse Train Input
Function Selection
New parameter
0: Frequency reference
1: PID feedback value
2: PID setpoint value
—
—
—
H6-02
Pulse Train Input Scaling
New parameter
—
—
—
H6-03
Pulse Train Input Gain
New parameter
—
—
—
H6-04
Pulse Train Input Bias
New parameter
—
—
—
H6-05
Pulse Train Input Filter
Time
New parameter
—
—
—
H6-06
Pulse Train Monitor
Selection
New parameter
—
—
—
H6-07
Pulse Train Monitor
Scaling
New parameter
L1-01
Motor Protection
Selection
MOL Fault Select
0:Disabled
1:Coast to Stop
See: GPD515/G5 E1-02
L1-01
Motor Overload
Protection Selection
Modified function
0: Disabled
1: Fan Cooled <10:1 motor
2:Blower Cooled 10:1 motor
3: Vector Motor 1000:1 motor
—
—
—
L1-03
Motor Overheat Alarm
Operation Selection
New parameter
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
—
—
—
L1-04
Motor Overheat Fault
Oper ation Selection
New parameter
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
—
—
—
L1-05
Motor Temperature Input
Filter Time
New parameter
—
—
—
L2-07
Momentary Recovery
Time
New parameter
—
—
—
L2-08
Frequency Reduction
Gain at KEB Start
New parameter
L3-07
Stall Prevention
Function P Gain
—
—
—
Deleted in G7
L3-08
Stall Prevention
Function Integral Time
—
—
—
Deleted in G7
—
—
—
L3-11
OV Supression function
selection
New parameter
—
—
—
L3-12
OV suppression function
level
New parameter
L4-05
Frequency Loss
Detection Selection
0: Stop
1: Run@ 80% PrevRef
L4-05
Frequency Reference Loss
Detection Selection
Modified function
0: Normal Operation - Drive will run at the
frequency reference.
1: Run at L4-06 PrevRef
Drive will run at the
percentage set in L4-06
—
—
—
L4-06
Frequency Reference
Level at Loss Frequency
New parameter
PL.G7.02.TransitionGuide 4/21/04
Page 32 of 38