beautypg.com

Yaskawa GPD 515/G5 to G7 User Manual

Page 24

background image

Product Transition Guide

GPD515/G5 to G7

PL.G7.02.TransitionGuide 4/21/04
Page 24 of 38
Yaskawa Electric America, Inc

GPD515/G5 Parameters

G7 Parameters

Parameter

No.

Name

(Digital Operator Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

A1-01 Access Level

0: Operation Only
1: User Level
2: Quick-Start [Q]
3: Basic Level [B]
4: Advanced Level [A]

A1-01


Access Level Selection

Removed:
3: Basic Level [B]

Modified selection:
2: Advanced Level

A1-02



Control Method Selection


0: V/F control without PG
1: V/F control with PG
2: Open Loop Vector
3: Flux Vector

A1-02



Control Method Selection


Additional function:
4: Open Loop Vector control 2

B1-01 Reference Selection

0: Operator
1: Terminals
2: Communication Serial Com
3: Option PCB
4: EWS Reference from CP-717

b1-01 Reference Selection

Changed to:
4: Pulse Input



B1-02 Operation Method

Selection

0: Operator
1: Terminals
2: Communication Serial Com
3: Option PCB
4: EWSRun from CP-717

b1-02 Run Command Selection Removed selection 4:

4: EWSRun from CP-717



B3-01 Speed Search Selection at

Start

0: Disabled
1: Enabled

b3-01 Speed Search Selection

Modified selections:
0: Speed Estimation Speed Search Disable
1: Speed Estimation Speed Search Enable
2: Current Detection Speed Search Disable
3: Current Detection Speed Search Enable

— —

b3-05 Speed Search Delay Time New Parameter

— —

b5-15 Sleep Function Start Level New Parameter

— —

b5-16 Sleep Delay Time

New Parameter

— —

b5-17 PID Accel/Decel Time

New Parameter

B8-03 Energy -saving Mode

Selection

0:Disabled
1:Enabled

b8-01 Energy Saving Control

Selection

Changed Parameter No.

B8-04 Energy-saving Control

Gain

b8-02 Energy Saving Gain

Changed Parameter No.

B8-05 Energy-saving Control

Time Constant

b8-03 Energy Saving Control

Filter Time Constant

Changed Parameter No.

— —

b8-04 Energy Saving Coefficient

Value

New Parameter

— —

b8-05 Power Detection Filter

Time

— —

b8-06 Search Operation Voltage

Limit

Output Voltage Limit

0:Disabled

C3-06

Operation Selection

1:Enabled

C3-05 Output Voltage Limit

Opera tion Selection

Changed Parameter No.