Product Transition Guide

Appendix 2- Parameter Differences

____________________________

PL.G7.02.TransitionGuide 4/21/04

Page 25 of 38

Yaskawa Electric America, Inc

GPD515/G5 Parameters

G7 Parameters

Parameter

No.

Name

(Digital Operator Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

— —

C6-02

Carrier Frequency
Selection

New parameter function different than old
C6-02 in GPD515/G5
0: Low noise
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program Determined by the settings of C6-
03 thru C6-05

C6-01 Carrier Frequency Upper

Limit

C6-03

Carrier Frequency
Upper Limit

Changed Parameter No.

C6-02 Carrier Frequency Lower

Limit

C6-04

Carrier Frequency
Lower Limit

Changed Parameter No.

C6-03 Carrier Frequency

Proportional Gain

C6-05

Carrier Frequency
Proportional Gain

Changed Parameter No.

New Parameter

— —

C6-11

Carrier Frequency
Selection Open Loop
Vector Control 2

Select the carrier frequency when open loop
vector control 2 is used.
1: 2 kHz
2: 4 kHz
3: 6 kHz
4: 8 kHz

C7-01 Hunting Prevention

Selection

0:Disabled
1:Enabled

n1-01

Hunting Prevention
Selection

Changed Parameter No.

C7-02 Hunting Prevention Gain

n1-02

Hunting Prevention Gain
Setting

Changed Parameter No.

C8-08 AFR Gain

n2-01

Speed Feedback Detection
Control AFR Gain

Changed Parameter No.

C8-09 AFR Time Constant

n2-02

AFR Time

Changed Parameter No.

— —

n2-03

Speed Feedback Detection
Control
AFR Time Constant 2

New parameter
Sets the time constant to control the amount
of change in the speed at low speed.

— —

d1-09

Frequency Reference 9

New Parameter

— —

d1-10

Frequency Reference 10

New Parameter

— —

d1-11

Frequency Reference 11

New Parameter

— —

d1-12

Frequency Reference 12

New Parameter

— —

d1-13

Frequency Reference 13

New Parameter

— —

d1-14

Frequency Reference 14

New Parameter

— —

d1-15

Frequency Reference 15

New Parameter

— —

d1-16

Frequency Reference 16

New Parameter

D1-09 Jog Frequency Reference

d1-17

Jog Frequency Reference Changed Parameter No.

— —

d2-03

Master Speed Reference
Lower Limit

New Parameter

— —

d6-01

Magnetic Field Weakening
Level

New Parameter

— —

d6-02

Magnetic Field Frequency New Parameter