Start up 4 - 6 – Yaskawa E7 Drive User Manual User Manual
Page 70

Start Up 4 - 6
Ensure the DATA/ENTER key is pressed to enter the selection in the Drive. “Entry Accepted” briefly appears and
the display is now no longer flashing.
9. Press the S key once to display E2-01 “Motor Rated FLA”.
This parameter is the foundation of motor protection. It can be entered when auto-tuning is performed. Set this
parameter according to the motor rated current (FLA). Press the DATA/ENTER key once. Use the S,▼, and X keys
to adjust E2-01 to the motor rated full load amps.
Ensure the DATA/ENTER key is pressed to enter the value in the Drive. “Entry Accepted” briefly appears and your
display is now flashing.
10. Press the ESC once. Press DATA/ENTER once. Press S key twice to display b1-02 “Run Source”. This parameter
selects where the Drive will receive the run command. Press the DATA/ENTER key once. Use the
S or ▼ keys and
the DATA/ENTER key to set this parameter for the application.
Ensure the DATA/ENTER key is pressed to enter the selection in the Drive. “Entry Accepted” briefly appears and
the display is now not flashing.
11. Press the
▼
key once to display b1-01 “Reference Source”. This parameter selects where the Drive will receive the
speed command. Press the DATA/ENTER key once. Use the S or ▼ keys and the DATA/ENTER key to set this
parameter for the application.
Table 4.2 Input Voltage Setting
Parameter
No.
Parameter Name
Digital Operator Display
Setting Range
Factory Setting
Menu Location
E1-01
Input Voltage Setting
Input Voltage
155.0 to 255.0
(208-240Vac)
240.0
(208-240Vac)
Quick Setting
or
Programming
310.0 to 510.0
(480Vac)
480.0
(480Vac)
Table 4.3 Motor Rated Current
Parameter
No.
Parameter Name
Digital Operator Display
Setting
Range
Factory
Setting
Menu
Location
E2-01
Motor Rated Current
Motor Rated FLA
kVA
Dependent
kVA
Dependent
Quick Setting
or
Programming
Table 4.4 Run Command Selection
Parameter
No.
Parameter Name
Digital Operator Display
Setting Choices
Setting
Range
Factory
Setting
Menu Location
b1-02
Run Command Selection
Run Source
0: Operator
1: Terminals
2: Serial Com
3: Option PCB
0 - 3
1
Quick Setting
or
Programming
TM_E7_01_07182008.book Page 6 Wednesday, July 23, 2008 2:35 PM