beautypg.com

Parameters a - 20, Table a.1 – Yaskawa E7 Drive User Manual User Manual

Page 188

background image

Parameters A - 20

Stall Prevention

L3-01

Stall Prevention Selection During
Accel
StallP Accel Sel

0: Disabled (Motor accelerates at active acceleration,

C1-01 or C1-03. The motor may stall if load is too
heavy or accel time is too short).

1: General Purpose (When output current exceeds L3-

02 level, acceleration stops. It starts to accelerate at
current value recovery).

2: Intelligent (The active acceleration rate, C1-01 or

C1-02, is ignored. Acceleration is completed in the
shortest amount of time w/o exceeding the current
value set in L3-02).

0 to 2

1

Programming

L3-02

Stall Prevention Level During
Accel
StallP Accel Lvl

This function is enabled when L3-01 is “1” or “2”.
Drive rated current is 100%. Decrease the set value if
stalling occurs at factory setting.

0 to 200

120%

Programming

L3-04

Stall Prevention Selection During
Decel
StallP Decel Sel

0: Disabled (The drive decelerates at the active decel-

eration rate, C1-02 or C1-04. If the load is too large
or the deceleration time is too short, an OV fault may
occur).

1: General Purpose (The drive decelerates at the active

deceleration rate, C1-02 or C1-04, but if the main cir-
cuit DC bus voltage reaches the stall prevention level
the output frequency will clamp. Deceleration will
continue once the DC bus level drops below the stall
prevention level).

2: Intelligent (The active deceleration rate is ignored

and the drive decelerates as fast as possible w/o
hitting OV fault level).

0 to 3

1

Programming

L3-05

Stall Prevention Selection During
Run
StallP Run Sel

0: Disabled (Drive runs a set frequency). A heavy load

may cause the drive to trip on an OC fault.

1: Decel Time 1 (In order to avoid stalling during heavy

loading, the drive will start to decelerate at Decel
time 1 (C1-02) if the output current exceeds the level
set by L3-06. Once the current level drops below the
L3-06 level the drive will accelerate back to its set
frequency at the active acceleration rate).

2: Decel Time 2 (Same as setting 1 except the drive

decelerates at Decel Time 2 (C1-04).
For 6Hz or less frequency, stall prevention function
during run is disabled regardless of L3-05 set.

0 to 2

1

Programming

L3-06

Stall Prevention Level During
Running
StallP Run Level

This function is enabled when L3-05 is “1” or “2”.
Drive rated current is set as 100%.
Normally, changing the setting is not required.
Decrease the set value if stalling occurs at factory
setting.

30 to 200

120%

Programming

Table A.1

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

TM_E7_01_07182008.book Page 20 Wednesday, July 23, 2008 2:35 PM

This manual is related to the following products: