Auto-tuning faults, Auto-tuning faults -13, Diagnostic & troubleshooting 6 - 13 – Yaskawa E7 Drive User Manual User Manual
Page 149

Diagnostic & Troubleshooting 6 - 13
Auto-Tuning Faults
Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and
the motor coasts to a stop during operation. The fault contact is not activated.
Table 6.4 Auto-Tuning Displays and Processing
Digital Operator Display
Probable Cause
Corrective Action
Er - 01
Fault
•There is an error in the data input
for autotuning.
•There is an error in the relationship
between the motor output and the
motor rated current.
• Check input data.
• Check Drive and motor capacity.
• Check motor rated current.
Er - 02
Minor Fault
A minor fault is detected during
auto-tuning.
• Check input data.
• Check wirings and around the
machine.
• Check the load.
Er - 03
STOP key
The STOP key is pressed during
auto-tuning, and the auto-tuning is
interrupted.
–
Er - 04
Resistance
Auto-tuning is not completed within
the specified time.
The auto-tuning result became other
than the parameter set range.
• Check input data.
• Check motor wiring.
• If a motor and a machine are
connected, disconnect the motor
from the machine.
Er - 12
I-det. Circuit
•Current flow exceeded the motor
rated current.
•Current detection value symbol was
reversed.
•Any of U/TI, V/T2, and W/T3 has
open-phase.
• Check current detection circuit,
wiring and mounting procedure.
Er - 13
Leakage Inductance Fault
Auto-tuning did not finish within the
set time.
Tuning result became other than the
parameter setting range.
• Check motor wiring.
End - 3
Data Invalid
Rated current set value is set too
high.
• Check input data (especially, motor
output current and motor rated cur-
rent value).