Yaskawa input assemblies, Yaskawa modbus message - input instance 100 (64h), Yaskawa input assemblies -3 – Yaskawa CM013 V7 DeviceNet Option User Manual
Page 24

Supported Objects 2-3
Yaskawa Input Assemblies
Yaskawa Modbus Message – Input Instance 100 (64h)
Yaskawa Standard Control – Input Instance 101 (65h)
Yaskawa Enhanced Control/Modbus Message – Input Instance 105 (69h)
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
100 (64h)
MODBUS
Message
0
Function Code (Only Modbus functions register read (03h) and register write (10h) are supported)
1
Register Number
2
3
Data
4
Note:
Refer to output instance 150 (96h) for response
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
101 (65h)
Standard
Control
0
-
Terminal S7
Terminal S6
Terminal S5
Terminal S4
Terminal S3
Run REV
Run FWD
1
Terminal P2
Terminal P1
Terminal
MA/MB
-
-
-
Fault Reset
External
Fault
2
Speed Reference (Scaled by Parameter n035)
3
4
Reserved
5
6
Reserved
7
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
105 (69h)
Enhanced
Control/
MODBUS
Message
0
-
Terminal S7
Terminal S6
Terminal S5
Terminal S4
Terminal S3
Run REV
Run FWD
1
Terminal P2
Terminal P1
Terminal
MA/MB
-
Function
Bit 2
1
Function
Bit 1
1
Fault
Reset
External
Fault
2
Speed Reference (Scaled by Parameter n035)
3
4
Register Number
5
6
Data
7
Note:
Refer to output instance 155 (9Bh) for response
1
Bit 1
Bit 2
Function
0
0
No Function
0
1
Read Register
1
0
Write Register
1
1
No Function