Configure the v7 drive, Command and reference source, Speed scaling – Yaskawa CM013 V7 DeviceNet Option User Manual
Page 19: Configure the v7 drive -14

Installation 1-14
Configure the V7 Drive
Command and Reference Source
The run/stop and frequency reference commands can originate from the operator keypad, external terminals or the V7 DeviceNet Option.
Parameter n003 (Operation Method Selection) sets the source of the run/stop commands. Parameter n004 (Reference Selection) sets the
source of the frequency reference. The run/stop and frequency reference commands may have different origins. For example, the run/stop
command may be set to External Terminals (n003 = 1) while the Frequency Reference may be set to Option (DeviceNet Option) (n004 = 9).
Note:
1
RS485 communications is disabled with the DeviceNet Option installed.
Speed Scaling
Since DeviceNet displays the motor speed and frequency reference in RPM, it is important to set the appropriate number of motor poles in
parameter n035.
Table 1.6 Reference and Operation Source Selection
Addr
Param
Function
Data
Description
Default
103h
n003
Operation Method
Selection
0
Operator keypad
1
1
Terminal
2
Serial Communication
1
3
Option kit - (V7 DeviceNet Option)
104h
n004
Reference Selection
0
Operator keypad potentiometer
2
1
Operator keypad
2
Voltage Reference (0-10VDC)
3
Current Reference (4-20mA)
4
Current Reference (0-20mA)
5
Pulse Train Reference
6
Serial Communication
1
7
Multifunction Analog Input (0-10VDC)
8
Multifunction Analog Input (4-20mA)
9
Option kit - (V7 DeviceNet Option)
Table 1.7 – Reference Display Selection
n035
Digital Operator Display Mode
0
Hz
1
%
2 … 39
DeviceNet displays the motor speed in RPM.
Enter the number of motor poles to set the input and output speed to RPM.
40 … 3999
User Scaling