Supported Objects 2-2

Supported Input Assemblies

‹

Basic Speed Control – Input Instance 20 (14h)

‹

Extended Speed Control – Input Instance 21 (15h)

‹

Speed and Torque Control – Input Instance 22 (16h)

‹

Extended Speed and Torque Control – Input Instance 23 (17h)

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

20 (14h)

Basic Speed

Control

4 Bytes

0

-

-

-

-

-

Fault Reset

-

Run FWD

1

-

2

Speed Reference (Scaled by Parameter n035)

3

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

21 (15h)

Extended

Speed

Control

4 Bytes

0

-

NetRef

1

NetCtrl

1

-

-

Fault Reset

Run REV

Run FWD

1

-

2

Speed Reference (Scaled by Parameter n035)

3

Note:

1

NetRef – When set, sets reference source (n004 = 9) to Option Card. When reset, returns n004 to its original setting.

NetCtrl – When set, sets Run command source (n003 = 3) to Option Card. When reset, returns n003 to its original setting.

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

22 (16h)

Basic Speed

and Torque

Control

6 Bytes

0

-

-

-

-

-

Fault Reset

-

Run FWD

1

-

2

Speed Reference (Scaled by Parameter n035)

3

4

Reserved

5

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

23 (17h)

Extended

Speed and

Torque

Control

6 Bytes

0

-

NetRef

1

NetCtrl

1

-

-

Fault Reset

Run REV

Run FWD

1

-

2

Speed Reference (Scaled by Parameter n035)

3

4

Reserved

5

Note:

1

NetRef – When set, sets reference source (n004= 9) to Option Card. When reset, returns n004 to its original setting.

NetCtrl – When set, sets Run command source (n003 = 3) to Option Card. When reset, returns n003 to its original setting.