10 Sub-Commands
YASKAWA ELECTRIC SIEP C730600 62B 1000-Series Option SI-ET3 Technical Manual
43
39
SEL_MON 5/6
Use the SEL MON5/6 command to select the contents of MON5 with bits 0 to 3 and to select the
contents of MON6 with bits 4 to 7.
Refer to
for the selection ranges for SEL REF5/6 and SEL MON5/6.
40
Reference selected with
SEL_REF3
Reference selected with SEL_REF3 (Lower)
41
Reference selected with SEL_REF3 (Upper)
42
Not used (Ignored if a value is set.)
43
Not used (Ignored if a value is set.)
44
Reference selected with
SEL_REF4
Reference selected with SEL_REF4 (Lower)
45
Reference selected with SEL_REF4 (Upper)
46
Not used (Set to 0.)
47
Not used (Set to 0.)
48
Reference selected with
SEL_REF5
Reference selected with SEL_REF5 (Lower)
49
Reference selected with SEL_REF5 (Upper)
50
Not used (Set to 0.)
51
Not used (Set to 0.)
52
Reference selected with
SEL_REF6
Reference selected with SEL_REF6 (Lower)
53
Reference selected with SEL_REF6 (Upper)
54
Not used (Set to 0.)
55
Not used (Set to 0.)
56
Reserved (0)
Not used
x
x
63
INV_IO Response
Byte
Command
Description
32
INV_IO (51H)
Command code
33
SUB_STAT
Refer to
SUB_STAT (Sub-Command Status) on page 39
.
34
35
36
SEL_REF 3/4
The value set in the command.
37
SEL_REF 5/6
The value set in the command.
38
SEL_MON 3/4
The value set in the command.
39
SEL_MON 5/6
The value set in the command.
40
Monitor data set to
SEL_MON3
Monitor data set to SEL_MON3 (Lower)
41
Monitor data set to SEL_MON3 (Upper)
42
Not used (Set to 0.)
43
Not used (Set to 0.)
44
Monitor data set to
SEL_MON4
Monitor data set to SEL_MON4 (Lower)
45
Monitor data set to SEL_MON4 (Upper)
46
Not used (Set to 0.)
47
Not used (Set to 0.)
48
Monitor data set to
SEL_MON5
Monitor data set to SEL_MON5 (Lower)
49
Monitor data set to SEL_MON5 (Upper)
50
Not used (Set to 0.)
51
Not used (Set to 0.)
52
Monitor data set to
SEL_MON6
Monitor data set to SEL_MON6 (Lower)
53
Monitor data set to SEL_MON6 (Upper)
54
Not used (Set to 0.)
55
Not used (Set to 0.)
56
Reserved (0)
Not used
x
x
63
INV_IO Command
Byte
Command
Description