Prm_wr: 02h (write parameter sub-command) – Yaskawa SI-ET3 User Manual
Page 27

9 Main Command
YASKAWA ELECTRIC SIEP C730600 62B 1000-Series Option SI-ET3 Technical Manual
27
Example: Reading C1-01 (200H)
PRM_WR: 02H (Write Parameter Sub-Command)
The PRM_WR command is used to write a parameter by specifying the parameter number, data size, and parameter data.
The command can be used in communication phases 2 and 3. The CONFIG command must be sent to set up after the
parameters are written. Refer to the drive instruction manual for details of MEMOBUS/Modbus register numbers.
PRM_RD Response
Byte
Response
Description
0
PRM_RD (01H)
Command code
1
RWDT
Watchdog data
2
CMD_STAT
Refer to
Command Status (CMD_STAT) on page 24
.
If the SIZE data is invalid or MEMOBUS/Modbus register number does not exist, “9” is set for CMD_ALM.
3
4
NO
MEMOBUS/Modbus register number (Lower) set in the command.
5
MEMOBUS/Modbus register number (Upper) set in the command.
6
SIZE
The SIZE is the same as the register number set in MEMOBUS/Modbus transfers.
7
Reserved (0)
0 is set.
8
PARAMETER
Sets the data read in the byte set in the command. The option stores the data read for PARAMETER from
lower byte (LSB) to upper byte (MSB). 0 is stored when the field is not used.
0 is stored in PARAMETER when command error occurs.
9
10
x
x
31
Byte
Command
Response
4
00H
00H
5
02H
02H
6
02H
02H
7
00H
00H
8
00H
Value set to C1-01 (Lower)
9
00H
Value set to C1-01 (Upper)
PRM_WR Command
Byte
Command
Description
0
PRM_WR (02H)
Command code
1
WDT
Watchdog data
2
CMD_CTRL
Refer to
Command Control (CMD_CTRL) on page 24
.
3
4
NO
MEMOBUS/Modbus register number (Lower)
5
MEMOBUS/Modbus register number (Upper)
6
SIZE
Set the data size in byte.
Available setting values are 2, 4, 6, and 8
7
Reserved (0)
Not used
8
PARAMETER
Specify the lower byte (LSB) before the upper byte (MSB) in the size set in the SIZE.
9
10
x
x
31
PRM_WR Response
Byte
Response
Description
0
PRM_WR (02H)
Command code
1
RWDT
Watchdog data