background image

Technical Data

SMA Solar Technology AG

76

SMC46-60A11-IA-en-81

Installation Manual

11.2 General Data

11.3 Protective Devices

Width x height x depth with
Electronic Solar Switch

468 mm x 613 mm x 242 mm

Weight

63 kg

Length x width x height of packaging

396 mm x 803 mm x 596 mm

Transport weight

68 kg

Climatic class as per IEC 60721-2-1

4K4H

Operating temperature range

− 25°C ... +60°C

Maximum permissible value for relative humidity,
non-condensing

100%

Maximum operating altitude above MSL

2,000 m

Noise emission (typical)

≤ 42 dB(A)

Power loss in night operation

0.25 W

Topology

LF transformer

Cooling concept

OptiCool

Fan connection

designed as safe disconnection in accordance

with DIN EN 50178:1998-04

Degree of protection for electronics according to
IEC 60529

IP65

Protection class according to IEC 62103

I

DC reverse polarity protection

short-circuit diode

Input-side disconnection device

Electronic Solar Switch

DC overvoltage protection

thermally monitored varistors

AC short-circuit current capability

current control

Grid monitoring

SMA Grid Guard 2.1

Maximum permissible fuse protection

40 A

Earth fault monitoring

Insulation monitoring: R

iso

> 1 MΩ

Galvanic isolation

available