5.2 Connection to the Electricity Grid (AC)
5.2.1 Conditions for the AC Connection
Cable Dimensioning
Use Sunny Design Version 2.0 or higher for sizing the conductor cross-sections (see design software
"Sunny Design" at www.SMA-Solar.com).
Cable Requirements
F
Terminals for the SMA Power Balancer
G
Flat male tab for earthing the cable shield when connecting the SMA Power Balancer
H
Additional terminal for earthing
I
Terminals for AC cables
K
Cable glands for the SMA Power Balancer
L
Cable gland for the AC cable
M
Cable glands for communication
N
Screw fixture of shield connection terminal for data cable
O
DC connector
P
Connection socket for the Electronic Solar Switch (ESS)
Q
Varistors
Connection requirements of the network operator
Always observe the connection requirements of your network operator.
Halving the cable losses
If three inverters with symmetrical feed-in are combined to form a three-phase system, the
neutral conductor is not subject to any load and the cable losses are halved. Thus, the
maximum possible cable length is doubled.
Item
Description
Value
A
External diameter
12 mm … 25 mm
B
Conductor cross-section
6 mm² … 16 mm²
C
Stripping length
approx. 16 mm