beautypg.com

4 connecting the pv array (dc), 1 conditions for dc connection, Connecting the pv array (dc) – SMA SMC 4600A Installation User Manual

Page 27: Conditions for dc connection

background image

SMA Solar Technology AG

Electrical Connection

Installation Manual

SMC46-60A11-IA-en-81

27

5.4 Connecting the PV Array (DC)

5.4.1 Conditions for DC Connection

• Requirements for the PV modules of the connected strings:

– same type
– same quantity
– identical alignment
– identical tilt

• The connection cables of the PV modules must be equipped with connectors. The connectors

required for DC connection are included in the scope of delivery.

• The following thresholds at the DC input of the inverter must not be exceeded:

Using Y adaptors for the parallel connection of strings
Y adaptors must not be visible or freely accessible in close proximity to the inverter.

• The DC circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter as described in Section 7.2

"Opening the Inverter" (page 48).

Maximum input voltage

Maximum input current

600 V (DC)

26.0 A (DC)

WARNING!
Danger to life due to electric shock or fire

The maximum possible input current per string is limited by the connectors used. If the
connectors are overloaded, an electric arc may occur and there is a risk of fire.

• Ensure that the input current per string does not exceed the maximum through-fault

current of the connectors used.

This manual is related to the following products: