SMA SMC 4600A Installation User Manual
Page 75
SMA Solar Technology AG
Technical Data
Installation Manual
SMC46-60A11-IA-en-81
75
AC Output
* Applies to SMC 6000A-11
** Applies to SMC 6000A
Efficiency
Rated power at 230 V, 50 Hz
6,000 W
Maximum apparent AC power
6,000 VA
Rated grid voltage
230 V
AC nominal voltage
220 V / 230 V / 240 V
AC voltage range
160 V ... 265 V
Nominal AC current at 230 V
26 A
Nominal AC current at 240 V
25 A
Maximum output current
26 A
Total harmonic factor of the output current with
AC voltage < 2% and
AC power > 50% of the rated power
≤ 3%
Rated mains frequency
50 Hz
AC mains frequency
50 Hz/60 Hz
Operating range at AC mains frequency of
50 Hz
44 Hz … 55 Hz
Operating range at AC mains frequency of
60 Hz
54 Hz … 65 Hz
Displacement power factor, adjustable*
0.8
overexcited
… 0.8
underexcited
Power factor at nominal AC power**
1
Feed-in phases
1
Connection phases
1
Overvoltage category according to
IEC 60664-1
III
Maximum efficiency, η
max
96.1%
European weighted efficiency, η
EU
95.3%