beautypg.com

4 assembly, 1 safety, 2 selecting the mounting location – SMA SMC 4600A Installation User Manual

Page 15: Assembly, Safety, Selecting the mounting location, 1 safety 4.2 selecting the mounting location

background image

SMA Solar Technology AG

Assembly

Installation Manual

SMC46-60A11-IA-en-81

15

4 Assembly

4.1 Safety

4.2 Selecting the Mounting Location

Take the following requirements into consideration when selecting the mounting location:

• The mounting method and location must be suitable for the inverter's weight and dimensions

(see Section 11 "Technical Data" (page 70)).

• Mount on a solid surface.
• The mounting location must be clear and safely accessible at all times without the use of

additional aids such as scaffolding or lifting platforms. If this is not the case, service work may
be restricted.

• Mount vertically or tilted backwards by max. 45°.
• The connection area must face downwards.

DANGER!
Danger to life due to fire or explosions

Despite careful construction, electrical devices can cause fires.

• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where highly flammable materials are stored.
• Do not mount the inverter in a potentially explosive atmosphere.

CAUTION!
Risk of burns due to hot enclosure parts

• Mount the inverter in such a way that it cannot be touched inadvertently.

CAUTION!
Risk of injury due to the heavy weight of the inverter

• Take the inverter's weight of approx. 63 kg into account when mounting.

This manual is related to the following products: