beautypg.com

SMA SC 500HE-US Maintenance Manual User Manual

Page 42

background image

4  Maintenance

SMA America, LLC

42

SC500HEUS-eng-WH-IUS120411

Maintenance Manual

5. Pull out the terminal plug for the heating control.

☑ A contactor audibly switches off the inverter. After about 2 minutes, another contactor

audibly switches off the control voltage.

✖ What if the switching of the contactors is not audible?

• Contact the SMA Service Line.

6. Check whether the heating elements radiate heat after a delay time of 5 minutes.

If the heating element does not radiate heat, contact the SMA Service Line.

7. Insert the terminal plug for the heating control.

☑ A contactor audibly switches on the control

voltage. After about 2 minutes, another
contactor audibly switches on the inverter.

✖ What if the switching of the contactors is not

audible?
• Contact the SMA Service Line.

8. Mount the protective covers.
9. Close the doors of the connection cabinet.

10. Close the doors of the inverter cabinet.

This manual is related to the following products: