4  Maintenance

SMA America, LLC

20

SC500HEUS-eng-WH-IUS120411

Maintenance Manual

Figure 4: Position of the miniature circuit-breaker

1. Set the key switch of the inverter to "Stop."

2. Check whether the DC and AC contactors audibly shut off within 5 seconds or less.

If the DC and AC contactors do not audibly shut off within 5 seconds or less, contact the
SMA Service Line.

3. Disconnect the inverter from the DC side of the PV array via the external DC disconnecting

device and ensure that it cannot be reconnected.

4. When using the Disconnect Unit:

– Disconnect the AC and DC sides using the Disconnect Unit's disconnect switch and ensure

that it cannot be reconnected (see the Disconnect Unit installation manual).

5. Disconnect the inverter on the AC side from the power distribution grid via the external

AC disconnecting device and ensure that it cannot be reconnected.

Position

Designation

A

Miniature circuit-breaker for the external control voltage

B

Miniature circuit-breaker for the internal control voltage

C

Miniature circuit-breaker for the voltage meter