4  Maintenance

Maintenance Manual

SC500HEUS-eng-WH-IUS120411

21

If there is no AC disconnecting device available, disconnect the AC voltage from the medium-
voltage transformer with the medium-voltage switch and ensure that it cannot be switched on
again.

6. Switch off the AC switch-disconnector.

7. Check whether the inverter's display shows 0 V DC voltage.

If the inverter's display does not show 0 V DC voltage, contact the SMA Service Line.

8. Check whether the inverter's display shows 0 V AC voltage.

If the inverter's display does not show 0 V AC voltage, contact the SMA Service Line.

9. In the case of additional external voltages:

– Disconnect additional external voltages and secure them against being switched back on.

11. If external control voltage is used, switch off the miniature circuit-breaker for the external control

voltage and secure it against being switched back on.

12. Switch off the miniature circuit-breaker for the internal control voltage and secure it against

being switched back on.

13. Switch off the miniature circuit-breaker for the voltage meter and secure it against being

switched back on.

14. Ensure that all poles are free of voltage.
15. Ground and short-circuit.
16. Cover or shield any adjacent live components.

☑ The Sunny Central is disconnected.

10.

%"/(&3

Electric shock from live voltage
The component parts of the Sunny Central are energized. Touching component parts of the
Sunny Central can result in severe injuries or death.

• After disconnecting the inverter, wait at least 10 minutes until the inverter's capacitors

have discharged completely.