4 Maintenance

This section includes all necessary information for performing maintenance work on the
Sunny Central.

4.1 Maintenance Intervals

Observance of maintenance intervals ensures trouble-free operation of the Sunny Central.
Maintenance intervals depend on ambient and operating conditions. Under especially harsh ambient
conditions, certain maintenance tasks must be performed more frequently. These maintenance tasks
are listed in the maintenance report. SMA recommends a monthly optical inspection in order to
determine the need for maintenance. Under normal ambient and operating conditions, the
Sunny Central must be completely serviced at the following intervals:

Maintenance under normal ambient and operating conditions:

Preventative replacement intervals:

Description

Interval

Routine maintenance

Every 24 months

AC circuit breaker

Every 48 months

Surge arrester

If tripped

Retighten the power cable connection by using a
cage clamp

Every 12 months

Unscheduled maintenance

After any short circuit

• Contact the SMA Service Line

Description

Interval

GFDI/soft grounding/ABB high-performance
circuit breaker

After 100 trippings

• Contact the SMA Service Line

Fan

10 years

• Contact the SMA Service Line

Surge arrester

• DEHNguard

If tripped

• Contact the SMA Service Line