4 maintenance, 1 maintenance intervals, Maintenance – SMA SC 500HE-US Maintenance Manual User Manual
Page 16: Maintenance intervals

4 Maintenance
SMA America, LLC
16
SC500HEUS-eng-WH-IUS120411
Maintenance Manual
4 Maintenance
This section includes all necessary information for performing maintenance work on the
Sunny Central.
4.1 Maintenance Intervals
Observance of maintenance intervals ensures trouble-free operation of the Sunny Central.
Maintenance intervals depend on ambient and operating conditions. Under especially harsh ambient
conditions, certain maintenance tasks must be performed more frequently. These maintenance tasks
are listed in the maintenance report. SMA recommends a monthly optical inspection in order to
determine the need for maintenance. Under normal ambient and operating conditions, the
Sunny Central must be completely serviced at the following intervals:
Maintenance under normal ambient and operating conditions:
Preventative replacement intervals:
Description
Interval
Routine maintenance
Every 24 months
AC circuit breaker
Every 48 months
Surge arrester
If tripped
Retighten the power cable connection by using a
cage clamp
Every 12 months
Unscheduled maintenance
After any short circuit
• Contact the SMA Service Line
Description
Interval
GFDI/soft grounding/ABB high-performance
circuit breaker
After 100 trippings
• Contact the SMA Service Line
Fan
10 years
• Contact the SMA Service Line
Surge arrester
• DEHNguard
If tripped
• Contact the SMA Service Line