11  Technical Data

Installation Manual

Communit-IA-A1-en-22

41

Nominal current

1.6 A to 0.7 A

Maximum back-up fuse

16.0 A

Type of connection*

Spring-cage terminals

Conductor cross-section for flexible cables

0.14 mm

2

to 2.5 mm

2

Conductor cross-section for rigid cables

0.08 mm

2

to 4 mm

2

* L, N and PE connection

Grid Connection of the Optional Customer Device at Installation Location 1
Voltage supply

230 V

AC

/

24 V

DC

Maximum power consumption at 230 V

AC

20 W

Maximum power consumption at 24 V

DC

depending on the option

Type of connection

X-COM

®

plug

Conductor cross-section

0.14 mm

2

to 1.5 mm

2

/

with bootlace ferrule 0.14 mm

2

to 1.0 mm

2

Grid Connection of the Optional Customer Device at Installation Location 2
Voltage supply

24 V

DC

Maximum power consumption at 24 V

DC

depending on the option

Type of connection

X-COM

®

plug

Conductor cross-section

0.14 mm

2

to 1.5 mm

2

/

with bootlace ferrule 0.14 mm

2

to 1.0 mm

2

Connection of the Sunny SensorBox
Type of connection

Spring-cage terminals

Number of insulated conductors and cable cross-section

2 x 2 x 0.14 mm

2

to 2 x 2 x 1.5 mm

2

Degree of Protection and Ambient Conditions
Degree of protection*

* as per EN 60529

IP54

Permissible ambient temperatures

–20°C to +50°C

Relative humidity**

** non-condensing

5% to 95%

Pollution degree***

*** as per DIN EN 50178:1997

2

Maximum altitude above mean sea level, MSL****

**** For installation altitudes above 2,000 m, the overvoltage category is reduced to class II.

4,000 m

Grid Connection