beautypg.com

SMA Communit-10 User Manual

Page 40

background image

11  Technical Data

SMA Solar Technology AG

40

Communit-IA-A1-en-22

Installation Manual

Ethernet I/O Module Moxa ioLogik E1242
Number of analog channels

4

Number of digital channels

4

Configurable digital inputs/outputs

4

Maximum conductor cross-section for connection at I/O

module

0.14 mm

2

to 1.5 mm

2

Analog Inputs of the I/O Modules Moxa ioLogik E1240 and E1242
Type

Differential input

Resolution

16 bit

I/O mode

Voltage/current

Input voltage range

0 V

DC

to 10 V

DC

/ 0 mA to 20 mA / 0 mA to 20 mA

Accuracy at 25°C / at –10°C to +60°C /

at –40°C to +75°C

±0.1% FSR / ±0.3% FSR / ±0.5% FSR

Digital Inputs of the I/O Module Moxa ioLogik E1242
Sensor type

Potential-free contact / wet contact (NPN or PNP)

I/O mode

Digital input or event counter

Potential-free contact

On: Short circuit to ground / Off: No-load operation

Wet contact NPN (DI to ground)

On: 0 V

DC

to 3 V

DC

/ Off: 10 V

DC

to 30 V

DC

Wet contact PNP (DI to ground)

Off: 0 V

DC

to 3 V

DC

/ On: 10 V

DC

to 30 V

DC

Number of inputs per COM

4

Digital Outputs of the I/O Module Moxa ioLogik E1242
Type

Sink

I/O mode

Digital output or pulse output

Pulse output frequency

500 Hz

Overvoltage protection

45 V

DC

Overcurrent protection

2.6 A (4 channels at 650 mA)

Overtemperature protection

minimum 150°C / typical 175°C

Current load

200 mA

Option-Dependent Interfaces
Communication

DSL / GSM / GPRS / EDGE / UMTS / Ethernet /

Speedwire / RS485 communication

Grid Connection
Nominal voltage

100 V to 240 V

Supply voltage

24 V

Frequency

50 Hz/60 Hz