beautypg.com

SMA MULTICLUSTER BOX 12 User Manual

Page 42

background image

12  Technical Data

SMA Solar Technology AG

42

MC-BOX-12-3-20-BE-en-10

Operating Manual

General Data

Number of line conductors

3

Permitted grid configuration

TN-S, TN-C-S and TT

Rated voltage between L and N

250 V

Rated voltage between L1 and L2

433 V

Rated voltage for auxiliary circuits 230 V

250 V AC

Rated frequency

50 Hz

Frequency range

45 Hz to 65 Hz

Rated impulse withstand voltage

4 kV

Width x height x depth (with base)

1,200 mm x 1,600 mm x 435 mm

(incl. 200 mm base)

Weight

200 kg

Maximum operating altitude above mean sea level

3,000 m

Inner subdivision

Form 1 (no subdivision)

Exterior design

closed type

Installation

only fixed interior installation permitted

Construction type

fixed components

Suitable for use by electrically qualified persons or unqualified

persons

Installation of the system and replacement of

equipment by electrically qualified persons only /

actuation of test buttons and read-off of information

by unqualified persons permitted

Measures for protection against electric shock

Basic protection afforded by insulation materials and

covers / fault protection by grounding conductors

and short-circuit protection devices / personal

protection by residual-current devices

Degree of protection of enclosure*

* in accordance with IEC 60529

IP55

Degree of protection with enclosure door open*

IP20

Pollution degree at the mounting location**

** in accordance with IEC 61439-1:2011

3

Pollution degree in the enclosure (micro-environment)

2

Protection class***

*** in accordance with IEC 417

1

Overvoltage category****

**** in accordance with EN 60664

Overvoltage category 3

EMC environment, emission**

B

EMC environment, interference immunity**

A

EC Declaration of Conformity

Yes

Operating temperature range*****

*****At operating temperatures of over 40°C the Sunny Island inverters reduce their output power (derating).

− 25°C to +60°C

Humidity

0% to 100%