SMA Solar Technology AG

12  Technical Data

Operating Manual

MC-BOX-12-3-20-BE-en-10

41

Connection of PV system

Connection of NA-Box / Grid Connect Box

Connection of grounding

Auxiliary electric circuits

Number of terminals

1 x 3-phase

Rated power

138 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V

AC current at rated values

3 x 200 A

Terminals for connection N, PE, L1, L2, L3

Spring-cage terminals

Maximum connectable conductor cross-section

150 mm

2

Unaffected short-circuit current / maximum relative rated

short-circuit current

10 kA

Maximum permissible back-up fuse

200 A

Number of terminals

1 x 3-phase

Rated input power

138 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V

Rated current / AC input current

3 x 200 A

Terminals for connection N, PE, L1, L2, L3

Spring-cage terminals

Maximum connectable conductor cross-section

150 mm²

Maximum unaffected short-circuit current / maximum relative

rated short-circuit current

10 kA

Maximum permissible back-up fuse

200 A

Width across flats for hexagon screws on the grounding busbar

AF 17

Maximum torque

15 Nm

Maximum connectable conductor cross-section

120 mm²

Fuse

10x38 cylinder fuse

Maximum permitted fuse rating

1 A