8. Switch on the circuit breaker of all three line conductors.
9. If the multifunction relay is used, switch on any supply voltage to the load.

☑ All three LEDs start to glow and the start-up phase begins. The start-up phase may take several

minutes.

☑ The green LED is glowing and the display alternates between the device type, the firmware

version, the serial number or designation of the inverter, the NetID, the configured country
data set and the display language.

✖ Green LED is flashing?

Possible cause of error: the DC input voltage is still too low or the inverter is monitoring the
utility grid.

• Once the DC input voltage is sufficiently high and the grid connection conditions are met,

the inverter will start operation.

✖ The red LED is glowing and an error message and event number appear in the display?

An error has occurred.

Rectify the error (see Section 4 "Troubleshooting", page 10).