Event number
Display message, cause and corrective measures
3501
Insulation failure > Check generator
The inverter has detected a ground fault in the PV array.
Corrective measures:
• Check the PV system for ground faults (see Section 7, page 28).
3601
High discharge curr. > Check generator
The leakage current of the inverter and the PV array is too high. There is a
ground fault, a residual current or a malfunction.
The inverter interrupts feed-in operation immediately after exceeding a limiting
value. When the fault is eliminated, the inverter automatically reconnects to the
utility grid.
Corrective measures:
• Check the PV system for ground faults (see Section 7, page 28).
3701
Resid.curr.too.high > Check generator
The inverter has detected a residual current due to temporary grounding of the
PV array.
Corrective measures:
• Check the PV system for ground faults (see Section 7, page 28).
3801 to 3802
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
• If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
3901 to 3902
Waiting for DC start cond. > Start cond. not met
The feed-in conditions for the utility grid are not yet fulfilled.
Corrective measures:
• Wait for higher irradiation.
• If this message is displayed frequently in the morning, increase the
voltage limit for starting grid feed-in. Change the parameter Critical
voltage to start feed-in.
• If this message is displayed frequently with medium irradiation, ensure
that the PV array is correctly rated.