Event number

Display message, cause and corrective measures

3501

Insulation failure > Check generator
The inverter has detected a ground fault in the PV array.
Corrective measures:

• Check the PV system for ground faults (see Section 7, page 28).

3601

High discharge curr. > Check generator
The leakage current of the inverter and the PV array is too high. There is a
ground fault, a residual current or a malfunction.
The inverter interrupts feed-in operation immediately after exceeding a limiting
value. When the fault is eliminated, the inverter automatically reconnects to the
utility grid.
Corrective measures:

• Check the PV system for ground faults (see Section 7, page 28).

3701

Resid.curr.too.high > Check generator
The inverter has detected a residual current due to temporary grounding of the
PV array.
Corrective measures:

• Check the PV system for ground faults (see Section 7, page 28).

3801 to 3802

DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:

• If this message is displayed frequently, ensure that the PV array has been

correctly rated and wired.

3901 to 3902

Waiting for DC start cond. > Start cond. not met
The feed-in conditions for the utility grid are not yet fulfilled.
Corrective measures:

• Wait for higher irradiation.
• If this message is displayed frequently in the morning, increase the

voltage limit for starting grid feed-in. Change the parameter Critical
voltage to start feed-in
.

• If this message is displayed frequently with medium irradiation, ensure

that the PV array is correctly rated.