Display message
Cause
Upd. language table
The inverter is updating the corresponding component.
Update display
The inverter is updating the corresponding component.
Update String prot.
The inverter is updating the corresponding component.
Update completed
The inverter has successfully completed the update.
Grid param. unchanged
The parameters are locked and you cannot change them.
Inst. code valid
The entered Grid Guard code is valid. Protected parameters have
now been unlocked and you can adjust the parameters. The param-
eters will be automatically locked again after ten feed-in hours.
4.3
Error Messages
Event number
Display message, cause and corrective measures
101 to 103
Grid fault
The grid voltage or grid impedance at the connection point of the inverter is
too high. The inverter has disconnected from the utility grid.
Corrective measures:
• Check whether the grid voltage at the connection point of the inverter is
permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid
conditions, contact the grid operator. The grid operator must agree with
an adjustment of the voltage at the feed-in point or with a change of the
monitored operating limits.
If the grid voltage is permanently within the permissible range and this
message is still displayed, contact Service.