Event number

Display message, cause and corrective measures

4001

String X defect. > Do not disconn. ESS
There is reverse current in the string displayed or the polarity of this string is re-
versed. Further strings could also be affected. The PV array is short-circuited. In
exceptional circumstances, this error message may be triggered by soiling or
shading of the modules (e.g. by leaves or snow).
Corrective measures:

• Disconnect the inverter from voltage sources when it is dark (see

Section 2.2, page 7)

• Check the design and the circuitry of the PV array.
• If irradiation is sufficient, check whether the same voltage is present at the

DC inputs A1 to A5.
If the same voltage is not present, one of the PV modules is possibly
defective.

4002

String X low power > Check generator
String-failure detection has detected a failed or weak string.
Corrective measures:

• Test the string that is shown in the message.

4003

String X defect. > Do not disconn. ESS
String-failure detection has detected a failed or weak substring.
Corrective measures:

Disconnect the inverter from all voltage sources (see Section 2.2, page 7)

.

• Check the design and the circuitry of the PV array.
• If irradiation is sufficient, check whether the same voltage is present at the

DC inputs A1 to A5.
If the same voltage is not present, one of the PV modules is possibly
defective.

4005

Part.str. X low p. > Check generator
String-failure detection has detected a failed or weak substring.
Corrective measures:

• Test the substring indicated in the message.

6001 to 6445

Self diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:

Contact Service (see Section 15, page 43).