7.
Damage to the fan due to compressed air
• Clean the fan only with a soft brush, a paint brush, or a damp cloth.
8. After cleaning, insert the fan plug back into the
pin connector until it snaps into place.
9. Insert the fan into the inverter until it snaps into place.
10. Push the fan guard into the retainer until it snaps into place.
11. Clean the fan on the left-hand side of the enclosure (see Section 5.2 "Cleaning the Fan on the
Left-Hand Side of the Enclosure", page 24).
5.2
Cleaning the Fan on the Left-Hand Side of the
Enclosure
1.
Danger to life due to electric shock
• Ensure that the inverter is disconnected from all voltage sources (see Section 2.2
"Disconnecting the Inverter from Voltage Sources", page 7).
2. Remove the ventilation grids on the left-hand and right-hand sides and clean them:
• Turn the rotary fastener of the ventilation
grid with a flat-blade screwdriver until the
notch is in a vertical position.
• Remove the ventilation grid. Use a
screwdriver to gently lever open the
ventilation grid.
• Clean the ventilation grid with a soft brush, a paint brush, or compressed air.