Event number

Display message, cause and corrective measures

7101

SD card defective
The SD memory card is not formatted.
Corrective measures:

• Re-format the SD memory card.
• Re-save the files to the SD memory card.

7102

Parameter file not found or defective
The parameter file was not found or is defective. The update failed. The in-
verter continues feeding power into the grid.
Corrective measures:

• Copy the parameter file into the card drive: \PARASET directory.

7105

Param. setting failed
It was not possible to set the parameter via the SD memory card. The inverter
continues feeding power into the grid.
Corrective measures:

• Check the parameters for valid values.
• Ensure change rights via SMA Grid Guard code.

7106

Update file defect.
Update file on the SD memory card is faulty.
Corrective measures:

• Re-format the SD memory card.
• Re-save the files to the SD memory card.

7110

No update file found
No update file has been found.
Corrective measures:

• Copy the update file in the SD memory card folder. Select the folder

\UPDATE.

7201 to 7202

Data stor. not poss.
Internal error. The inverter continues to feed into the utility grid.
Corrective measures:

• Contact Service.

7303

Update main CPU failed
The cause must be determined by the Service.
Corrective measures:

Contact Service (see Section 15, page 43).