6  Configuring the Module

Installation Manual

PCONTROLMOD-IA-en-15

31

6.3 Setting the Operating Mode of the Multifunction Relay

Procedure:

• Set the operating mode of the multifunction relay.
• If one of the following operating modes is used, you will need to carry out further settings for

the operating mode:

Self-consumption/SelfCsmp
Control via communication/ComCtl
Battery bank/BatCha

Setting the Operating Mode of the Multifunction Relay

By default, the multifunction relay is set to activate a fault indicator if an error occurs. If you wish to
use the multifunction relay for another purpose, you will need to set the operating mode.

• Select the parameter Operating mode of multifunction relay/Mlt.OpMode and set the

desired operating mode (see Section 4.3 "Multifunction Relay", page 11).

Settings for Operating Mode Self-Consumption/SelfCsmp

• Set the power threshold from which a load is to be switched on. Select the parameter Minimum

On time for MFR self-consumption/Mlt.MinOnPwr and set the desired power.

• Set the minimum time for which the power must exceed the set threshold in order to switch on

the load. Select the parameter Minimum On power for MFR self-consumption/
Mlt.MinOnPwr and set the desired minimum time.

• Set the minimum duration for which the load remains switched on. Select the parameter

Minimum On time for MFR self-consumption/Mlt.MinOnTmm and set the minimum
duration.

Settings for Operating Mode Control via Communication/ComCtl

• Set the status of the multifunction relay where it is to be controlled via a communication product.

Select the parameter Status of MFR with control via communication/MltComCtl.Sw and
set the status.

Settings for Operating Mode Battery bank/BatCha

• Set the power threshold from which the battery is to be charged. Select the parameter

Minimum on-power of MFR battery bank/Mlt.BatCha.Pwr and set the desired power.

• Set the minimum time which must elapse after charging the battery before it can be charged

again. Select the parameter Minimum On power for MFR battery bank/
Mlt.BatCha.Tmm and set the minimum time.