8 multifunction relay connection, 1 connection options for the multifunction relay – SMA 20000TL Installation User Manual
Page 24
5 Electrical Connection
SMA Solar Technology AG
24
PCONTROLMOD-IA-en-15
Installation Manual
Procedure:
1. Insert one end of the cable in inverter 1 and the other end in inverter 2. Each cable must be
routed through the seal and the cable gland of the inverter.
2. Connect a six-pole plug to each end of the cable as follows:
• Release the required conductor inlets of the plug using a screwdriver.
• Insert the insulated conductors into the conductor inlets. Make sure that the noted conductor
colors correspond to the pin assignment of the module.
3. In inverter 1, connect the six-pole plug to the free terminal for the ripple control receiver.
Observe the pin assignment.
4. In inverter 2, connect the six-pole plug to one of the terminals for the ripple control receiver.
Observe the pin assignment.
5. Fasten the swivel nut of the cable gland on both inverters hand-tight. Ensure that the cable is
securely in place and that the enclosure opening of the inverter is tightly sealed.
6. On both inverters, flip down the display and fasten the display screw hand-tight.
7. Close and commission both inverters (see inverter manual).
5.8 Multifunction Relay Connection
5.8.1 Connection Options for the Multifunction Relay
Depending on the required purpose of the multifunction relay, you can choose between the following
connection options (see Section 4.3 "Multifunction Relay", page 11):
Operating mode of
multifunction relay
(Mlt.OpMod)
Connection option
Fault indication (FltInd)
Using the multifunction relay as fault indicator contact
Self-consumption
(SelfCsmp)
Controlling loads or charging batteries in a power-dependent
way via the multifunction relay
Control via communication
(ComCtl)
Controlling loads or charging batteries in a power-dependent
way via the multifunction relay
Battery bank (BatCha)
Controlling loads or charging batteries in a power-dependent
way via the multifunction relay
Fan control (FanCtl)
Connecting the external fan (see fan documentation)
Switching status grid relay
(GriSwCpy)
Reporting the switching status of the grid relay