6 connecting the ripple control receiver, Multi-pole plugs – SMA 20000TL Installation User Manual
Page 19
SMA Solar Technology AG
Installation Manual
PCONTROLMOD-IA-en-15
19
5.5 Preparing the Connection Cables for Connection to
Multi-Pole Plugs
Always proceed as follows to prepare connection cables for connection to multi-pole plugs.
Procedure:
1. Trim 4 cm of the cable sheath at the end of the connection cable to be attached to the multi-pole
plug.
2. Trim unused insulated conductors flush with the cable sheath.
3. Strip off the conductor insulation by 6 mm.
5.6 Connecting the Ripple Control Receiver
Additionally required material (not included in the scope of delivery):
☐ One ripple control receiver with four outputs (see figure 5)
☐ One or two connection cables (see Section 5.2 "Cable Requirements", page 14)
Requirements:
☐ The connection cable must have been prepared for connection to the multi-pole plug (see
Section 5.5 "Preparing the Connection Cables for Connection to Multi-Pole Plugs", page 19).
☐ The enclosure opening on the inverter must be prepared (see Section 5.4 "Preparing the
Enclosure Opening on the Inverter", page 18).
Figure 5: Pin assignment of the module at the ripple control receiver terminals
Duplicate terminals for ripple control receiver
The ripple control receiver can be connected either to pins 1 to 5 or to pins 14 to 18.
The pins 1/18, 2/17, 3/16, 4/15 and 5/14 are each bridged so that a loop through of the
ripple control receiver signals is possible.