beautypg.com

6 connecting the ripple control receiver, Multi-pole plugs – SMA 20000TL Installation User Manual

Page 19

background image

SMA Solar Technology AG

Installation Manual

PCONTROLMOD-IA-en-15

19

5.5 Preparing the Connection Cables for Connection to

Multi-Pole Plugs

Always proceed as follows to prepare connection cables for connection to multi-pole plugs.

Procedure:

1. Trim 4 cm of the cable sheath at the end of the connection cable to be attached to the multi-pole

plug.

2. Trim unused insulated conductors flush with the cable sheath.
3. Strip off the conductor insulation by 6 mm.

5.6 Connecting the Ripple Control Receiver

Additionally required material (not included in the scope of delivery):

☐ One ripple control receiver with four outputs (see figure 5)
☐ One or two connection cables (see Section 5.2 "Cable Requirements", page 14)

Requirements:

☐ The connection cable must have been prepared for connection to the multi-pole plug (see

Section 5.5 "Preparing the Connection Cables for Connection to Multi-Pole Plugs", page 19).

☐ The enclosure opening on the inverter must be prepared (see Section 5.4 "Preparing the

Enclosure Opening on the Inverter", page 18).

Figure 5: Pin assignment of the module at the ripple control receiver terminals

Duplicate terminals for ripple control receiver
The ripple control receiver can be connected either to pins 1 to 5 or to pins 14 to 18.
The pins 1/18, 2/17, 3/16, 4/15 and 5/14 are each bridged so that a loop through of the
ripple control receiver signals is possible.

This manual is related to the following products: