5.2 Cable Requirements

☐ UV-resistant for outdoor use
☐ Cable diameter when using a single-hole seal (one cable per cable gland): 5 mm to 13 mm
☐ Cable diameter when using a two-hole cable seal (two cables per cable gland): 6.0 mm
☐ Conductor cross-section: 0.5 mm

2

to 1.5 mm

2

☐ Maximum cable length: 100 m
☐ Required number of insulated conductors for connecting the ripple control receiver: at least five
☐ Required number of insulated conductors for connecting to the multifunction relay: at least two

Position

Designation

A

Inverter display (flipped up)

B

Mounting position of the module

C

Cable route to the module

D

Cable gland M20 x 1.5

Common connection cable
You can use one connection cable with at least seven insulated conductors to connect both the
ripple control receiver and the multifunction relay.