5  Electrical Connection

SMA Solar Technology AG

28

PCONTROLMOD-IA-en-15

Installation Manual

5.8.2 Connecting the Remote Terminal to the Multifunction Relay

Requirements:

☐ You must select the connection option depending on the desired function of the multifunction

relay (see Section 5.8.1 "Connection Options for the Multifunction Relay", page 24).

☐ The technical requirements of the multifunction relay must be met (see Section 9 "Technical

Data", page 36).

☐ The enclosure opening on the inverter must be prepared (see Section 5.4, page 18).
☐ The connection cable must have been prepared for connection to the multi-pole plug

(see Section 5.5, page 19).

☐ Only use contactors which meet the connection requirements of the multifunction relay

(see Section 9 "Technical Data", page 36).

Figure 10: Pin assignment of the module at the multifunction relay terminal

Destruction of the multifunction relay as a result of excessive contact load

• Observe the maximum switching voltage and maximum switching current (see Section 9

"Technical Data", page 36).

• Only use suitable contactors (see Section 9 "Technical Data", page 36).

Pin

Signal

Explanation

9

NC

Back contact

8

NO

Front contact

7

CO

Change-over contact