5  Electrical Connection

SMA Solar Technology AG

20

PCONTROLMOD-IA-en-15

Installation Manual

Functions of Signals D1 to D4 in Operating Mode Remote Shutdown
(Default Settings for Italy)

Pin

Signal

Pin 5 / Pin 14

+ 12 V

Pin 4 / Pin 15

D4

Pin 3 / Pin 16

D3

Pin 2 / Pin 17

D2

Pin 1 / Pin 18

D1

D1

D2

D3*

* The signals D3 and D4 are not evaluated in the operating mode Remote shutdown.

D4*

Function

Closed

Closed

Open/Closed

Open/Closed

No specification

Open

Closed

Open/Closed

Open/Closed

Remote shutdown

Closed

Open

Open/Closed

Open/Closed

Narrowing of
frequency limits

Open

Open

Open/Closed

Open/Closed

Remote shutdown