Upgrading software – Grass Valley 2000NET v4.0.0 User Manual
Page 85
2000NET Instruction Manual
85
2000NET Software Update From FTP Server
Upgrading Software
With the FTPD running, use the 2000 GUI to initiate software updates. Use
the web-browser to:
•
Access the appropriate Software Update page for a given module,
•
Enter the required data into the HTML Form on that page, and
•
Submit the form.
The 2000 frame uses the data in the form to contact the FTPD on the
server, download the update file, and reprogram the targeted module.
Note
Prior to attempting update of software, refer to the target module’s manual
and confirm that the Remote/Local Only jumper is in the Remote position.
Note
To monitor the progress of the download, you may use the serial port con-
nection with a computer running a terminal emulation application.
a.
Open a web browser on a PC that is connected over the network to
the 2000 frame.
b.
Enter the URL of the frame where the module to be updated resides.
The frame’s main status page will appear.
c.
Click on the module’s link and then click on
Software Update
.
The module’s Software Update page will appear (
). This
form is the same for all 2000 modules that support network soft-
ware update.
Figure 60. Network Module Software Update Web Page
Use
this
link