Grass Valley 2000NET v4.0.0 User Manual
Page 63

2000NET Instruction Manual
63
Service
•
For Frame Bus Failure-Fixed events:
Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
FRAME BUS STATUS REPORTING
parameter on the
frame’s
CONFIGURATION
page is Enabled.
•
For Front Cover Removed -Installed events, check that the
COVER
STATUS REPORTING
parameter on the frame’s
CONFIGURATION
page is
Enabled.
•
For Frame Bus Failure-Fixed events:
Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
FRAME BUS STATUS REPORTING
parameter on the
frame’s
CONFIGURATION
page is Enabled.
•
For Cooling Fan Failure-Fixed events:
Check that the FAN switch (Switch 4) on the S1 DIP switch block of
the 2000NET module is Enabled, and
Check that the
FAN STATUS REPORTING
parameter on the frame’s
CON-
FIGURATION
page is Enabled.
•
For Module Health Failure-Fixed events,
Check that the MODULE switch (Switch 5) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
MODULE HEALTH REPORTING
parameter on the frame’s
CONFIGURATION
page is Enabled.
•
Check that the SNMP Manager is properly configured to receive the
Event Messages.
Check that the SNMP Manager has been assigned the same commu-
nity name as in the frame’s configuration.
6.
Check the network connectivity between the SNMP Manager and the
frame as described in the steps on