Status Monitoring and Reporting
continuous voltage level to the Module Health bus indicating that a
problem exists on the module but will not indicate what the problem is.
Alarms and SNMP Monitoring
Faults and alarms from the 2000NET module can be reported to a Frame
Health Alarm connector on the rear of the 2000T3 frame (see
) and/or to a networked SNMP monitoring
system (see
2000NET Module Alarm DIP Switches
Two eight-position DIP switches (S1 and S2) enable or disable the overall
fault and alarm reporting functions of the module. The current status of
these settings is reported on the Status web page of the 2000NET GUI
(
), the Frame Alarm Reporting web page (
), and the SNMP
Reporting web page (
). Disabling (or filtering) of fault reports can
also be useful in isolating problems in the frame.
The Frame Health Alarm on the rear of the Kameleon 2000 Series frame
responds directly to the settings of the DIP switches. Some media modules
provide enabling/disabling of Frame Health reporting for Slot Status,
Signal Loss and Reference Loss on the Slot Config web page for the media
module. Refer to
Media Module Slot Configuration on page 51
for the location of S1 and S2 and
for
the possible settings. A settings table is also silk-screened on the bottom of
the module.
Figure 15. DIP Switches S1 and S2
12345678
12345678
S2
S1
Power Supply #3
Power Supply #4
Power Supply #1
Power Supply #2
Fan
Module
Frame Bus
NM Control
Asynchronous Status
Frame Control