Installing the switch in a 19-inch rack, Requirements for the rack, Mounting brackets and rack-mounting rail kit – H3C Technologies H3C S5820V2 Series Switches User Manual
Page 13
5
Installing the switch in a 19-inch rack
Requirements for the rack
To close the rack door easily, make sure the rack depth for the S5830V2-24S, S5820V2-52QF
(LS-5820V2-52QF), S5820V2-52QF-U, and S5820V2-52Q switches is a minimum of 1000 mm (39.37
in).
The distance from the front to the rear posts of the rack must meet the requirements described in
.
Table 3 Requirements for the distance from the front to rear rack posts
Switch model
Installation method
Minimum distance
Maximum distance
S5830V2-24S
Using mounting brackets
and slide rails (provided)
401 mm (15.79 in)
895 mm (35.24 in)
•
S5820V2-48S
•
S5820V2-52QF
(LS-5820V2-52QF-H3)
•
S5820V2-52QF
(LS-5820V2-52QF-H5)
•
S5820V2-54QS-GE
Using mounting brackets
and slide rails (provided)
401 mm (15.79 in)
654 mm (25.75 in)
Using mounting brackets
and long slide rails
(optional)
621 mm (24.45 in)
874 mm (34.41 in)
•
S5820V2-52QF
(LS-5820V2-52QF)
•
S5820V2-52QF-U
•
S5820V2-52Q
Using mounting brackets
and slide rails (provided)
405 mm (15.94 in)
854 mm (33.62 in)
Mounting brackets and rack-mounting rail kit
The S5830V2&S5820V2 switches come with a pair of mounting brackets (see
) and a
rack-mounting kit that includes a pair of chassis rails and a pair of slide rails (see
).
Figure 2 1U mounting bracket kit