17. SAMSUNG PLC
17. SAMSUNG PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.
Select PLC Type
PLC
Connection
SPC series
SPC series
RS-232C
[Wiring Diagram 1]
RS-422/485
[Wiring Diagram 2]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
9600 bps
9600 bps
Parity
Not provided
Not provided
Stop bit
1
1
Terminating resistance
ON for RS-485
−
Memory
TYPE
Remarks
R
(input/output)
0
L
(link relay)
1
M
(internal relay)
2
K
(keep relay)
3
F
(special relay)
4
W
(data register)
5