4
1. Ethernet
4-43
Netw
Get Error Contents
int HKEtn_GetLastError()
• Error codes and solutions
Code
Contents
Solution
−1
Undefined command (receive timeout)
Check the command.
−2
Undefined IP address
Check the IP address.
−3
Target station busy
Reduce the frequency of communications.
−4
Illegal packet bytes
Check response processing at the target
station.
−5
Packet bytes exceed the maximum
number.
Reduce the send packet size.
−6
Local mode error
Check that the target station is in the RUN
mode.
−7
Preparing for communications
Start communications when the target
station is ready.
−8
Communication failure
–
Cannot access
Check the target station.
−9
Cannot process due to short memory
Check the memory space at the target
station.
−10
Illegal received data
Check the command.
−20
Socket initialization error
Check parameters for initialization.
−50
Requested packet byte exceeds the
maximum number.
Reduce the requested size.
−51
Address error
Check the requested memory type.
−52
Communication failure
–
Cannot access
Check the target station.
−54
Write protected
Check write-protection of the card.
−55
Cannot process due to short memory
Check the memory space at the target
station.
−56
Sampling buffer error
Check the command.
−100 Processing another command
Continue retrying.
−101 Command control
–
Buffer over
Reduce the frequency of communications.
−120 Communications aborted by the user
Communications are forcedly aborted.
−121 Received during command processing
Reduce the frequency of communications.