V-mdd (dual port interface), V-mdd (dual port interface) -17, Co nne c tio n to p l cs – Hakko MONITOUCH V7 series User Manual
Page 224
![background image](/manuals/79278/224/background.png)
5
1. MITSUBISHI PLC
5-17
Co
nne
V-MDD (Dual Port Interface)
V-MDD is the add-on connector with two ports, specifically designed for the connector on
MITSUBISHI’s A series, QnA series or FX series CPU programmer.
• The power to the V-MDD is supplied from the CPU. Check the electric capacity of 5 V
at the CPU. (Current consumption: max. 350 mA)
• Keep the cable between the CPU and V-MDD as short as possible. (Max. 1 to 1.5 m)
• Be sure to consider noise problems when performing wiring.
• When V-MDD is used for connection with the V7 series, set 1.5 seconds or above for
the timeout time in the [Comm. Parameter] dialog.
• Please read the instruction manual for V-MDD before use.
CPU
GD
G
P
P
V7
1 2 3
F1
F2
F3
F4
F5
F6
F7
SYSTEM
POWER
A6GPP, A7PHP, computer, etc.
MITSUBISHI A/QnA/FX series
MB-CPUQ cable (optional)
Slide switch
1:
A series
2:
QnA series
3:
FX series
*
Set the slide switch before turning
the power on.
When connecting to the CPU of MITSUBISHI A/QnA series:
Insert the connector on the backside into the CPU port
directly or use the MDD-CPU (optional) cable for
connection.
When connecting to the CPU of MITSUBISHI FX1/2 series:
Use the MDD-CPU cable (optional) for connection.
When connecting to the CPU of MITSUBISHI
FX2N/1N/0N/1S series:
Use MITSUBISHI’s conversion cable “FX-20P-CADP.”
V-MDD cannot be used with the MI4-FX cable.