Hidic-h: switch setting, Available memory, Hidic-h: switch setting -37 – Hakko MONITOUCH V7 series User Manual
Page 244: Available memory -37, Hidic-h
5
4. HITACHI PLC
5-37
Co
nne
HIDIC-H: Switch Setting
Baud rate:
19200 bps
MODE switch:
To connect to both RS-232C and RS-422, set MODE switch to 9.
RS-232C (protocol 2 without port) RS-422 (protocol 2 with port)
ST No switch:
“0” for both
Ч10, Ч1
DIP switch
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.
HIDIC-H
Switch
Setting
Contents
1
OFF
Bit length
2
OFF
Same as that set on V7 (normally 19200 bps)
3
ON
4
ON
5
ON
With parity
6
ON
Even
7
OFF
Stop bit 1
8
ON
With sumcheck
Memory
TYPE
Remarks
WR
(internal word output)
0
X
(external bit input)
1
WX as word device
Y
(external bit output)
2
WY as word device
L
(bit CPU link area)
3
WL as word device
M
(bit data area)
4
WM as word device
TC
(timer counter/elapsed time)
5
R
(relay)
6
TD
(timer counter/contact)
7
WN
(network input/output)
8