Error display, Error display -45, Communication errors – Hakko MONITOUCH V7 series User Manual
Page 196: Communication error, Ethernet 4-45
4
1. Ethernet
4-45
Netw
Error Display
Error messages displayed on the V7 series and those stored in the system memory are
explained.
Communication Errors
The Ethernet status is stored in system memory address $s518 of the V7 series during
Ethernet communications. The communication error occurs when a code other than “0”
(normal) is stored in system memory address $s518.
• In the RUN mode
• To check the occurrence of an error on the Main Menu screen:
Retry
Ethernet Error:XXXX
Screen No. :
Received Code No. :
Communication Error
* When [Continue] is selected for
[Comm. Error Handling] in the
[Detail] tab window of the [Comm.
Parameter] dialog, a following
screen is displayed.
The error number is displayed here.
Communication Error
Ethernet Error:XXXX
2002-4 -1 07:23:30
SYSTEM PROG. VER. 1.010
FONT
VER.1.300 / 1.000 / 1.000
ENGLISH
I/F DRV VER.1.310
YOKOGAWA FA-M3
Ethernet
Editor:MJ1
Main Menu
V 7 1 0 i T D
System Information
PLC Type : YOKOGAWAFA-M3/FA-M3R(Ethernet)
Comment :
Screen Data
Information
Size : 5783552
SRAM/Clock
Ethernet
Card
Menu
I/O Test
PORT: 10000
MAC: 0050FF000035
PORT: 10000
MAC: 0050FF000035 Error:XXX
Ethernet Information
Trans.Speed : 10BASE-T
Stat. No. : 192.168.1.68
Ethernet Information
Trans.Speed : 10BASE-T
Stat. No. : 192.168.1.68
Stop
0.50 sec
3
Error :
Time-Out :
Retry :
The error number is displayed here.