Users – Super Systems SDStatus User Manual
Page 46

SDStatus View and Workstation Operations Manual
Super Systems Inc.
Page 46 of 83
Figure 63 - Alarm Sound Times window
To add an alarm sound time, click the “Add Alarm Sound
Time” button. A window similar to the one shown in Figure
64 will appear. In this menu, you can select:
• The alarm group to which the alarm sound will
apply (“A”)
• The number of days, hours, and minutes that must
pass before the alarm will sound in Workstation
(“B”).
When the “Use Sound Frequency” box is checked, you can
also select:
• The frequency—in days, hours, and minutes—with
which the alarm sound will be repeated in
Workstation after the first alarm sound takes place
(“C”). Again, once an alarm is acknowledged in
Workstation, the alarm sound will not be repeated.
Figure 64 - Add Alarm Sound Time
window
To delete an existing alarm sound time, select the appropriate line and click the “Delete Alarm
Sound Time” button.
Users
SDStatus provides the option of requiring users to have certain access levels in order to
acknowledge alarms in Workstation. The Users option allows you to set up user names and
passwords with one of three different access levels: NoLevelSpecified, Operator, Supervisor,
and Administrator. These access levels are associated with the access levels specified for
alarms in Alarm Ack Levels (Alarm Acknowledgement Levels), which is covered in detail below.
A
B
C