5 - install sensor box 6 - electrical hook-up – Sloan 150 ES-SM Optima ES-SM Concealed Surface Mount Flushometer User Manual
Page 5

5
A
Be certain power is OFF to prevent damage to electrical
components. Connect all cables EXACTLY as shown.
D
Install Gasket (EL-456) and Wall Bracket (EL-460) onto Finished
Wall using two (2) #6 Phillips screws. Ensure that Sensor Lens
faces outward and horizontally from finished wall.
E
Feed the 15-Foot Cord With RJ-11 Plug through the Wall Bracket,
Gasket and 1” (25 mm) diameter hole.
F
Install Sensor Cover Plate and secure with Screw.
One 50 VA Transformer serves up to ten (10) OPTIMA Closet/Urinal Flushometers. Specify number of transformers required accordingly.
EL-497
URINAL
SENSOR
24 VAC POWER CORD
TO 24 VAC
TRANSFORMER
TO TERMINAL BLOCK
36-INCH CORD
WITH RJ-11 PLUG
24 VAC
TERMINAL
BLOCK
ETF-492-A
CONTROL MODULE
MODULAR
RECEPTACLES ARE
INTERCHANGEABLE
(CONNECTORS CAN
BE INSERTED INTO
ANY RECEPTACLE)
15-FOOT CORD WITH
RJ-11 PLUG
MODEL 194 ES-SM
SHOWN
1” (25 mm) DIAMETER HOLE
FINISHED
WALL
ETF-211 WALL
ANCHORS
(INSTALLED)
EL-456 GASKET
(FLAT SIDE TOWARD WALL)
EL-460 WALL
BRACKET
OVERRIDE BUTTON
(MODELS 150 & 152)
SENSOR
SCREW
ETF-212
(#6 PHILLIPS)
SCREWS
A
Refer to Page 2 Rough-in
drawings for the proper
location of the Sensor Box.
Position Gasket (EL-456) onto
Finished Wall in the Sensor Box
location just determined. Using
the Gasket as a template, mark
Mounting Holes and Sensor
Box Cable location.
B
Drill a 1/16” (1.6 mm) hole at the two Mounting Hole locations.
Drill a 1” (25 mm) hole at the Sensor Box Cable location.
C
Install an ETF-211 Wall Anchor in each Mounting Hole.
SENSOR BOX
CABLE HOLE
MOUNTING HOLES
EL-461
WATER CLOSET
SENSOR
24 VAC POWER CORD
TO 24 VAC
TRANSFORMER
TO TERMINAL BLOCK
36-INCH CORD
WITH RJ-11 PLUG
24 VAC
TERMINAL
BLOCK
ETF-492-A
CONTROL MODULE
MODULAR
RECEPTACLES ARE
INTERCHANGEABLE
(CONNECTORS CAN
BE INSERTED INTO
ANY RECEPTACLE)
15-FOOT CORD WITH
RJ-11 PLUG
MODEL 150 ES-SM
SHOWN
WATER CLOSET
URINAL
5 - INSTALL SENSOR BOX
6 - ELECTRICAL HOOK-UP