Falcon user guide – RLE FMS8 User Manual
Page 62
Falcon User Guide
62
** System Menu/Help **
SS - System Status
CA - Current Alarms
KA - Kill All Alarms
LM - Log Menu
TI - Display Date/Time
AD - ADC Input Values
MS - Modem Stats
NS - Network Stats
AT - Arp Table
SC - System Confi g
DU - Dump Network Packets
NT - Network Trace
PING - Ping an IP Address
EX - Exit to Bootloader
Enter Menu Selection >
Enter Menu Selection > SC ******
** Main Confi guration Menu **
1. System Menu
2. IP Confi g Menu
3. Modem Confi g menu
4. EIA-485 Confi g menu
5. Factory Menu
6. Load/Save Confi g Data
7. Confi guration Password
8. E-Mail, SMTP Confi g Menu
X. Exit
Enter Menu Selection >
Enter Menu Selection >1
System Confi guration Menu
1. System Name: Falcon Monitoring System
2. Clock: 10/27/00 16:37:17
3. Keypad Access
4. Inputs
5. Relays
6. Battery
7. Analog Averaging: 0
8. Persistent Traps: 0
9. Slave Inputs
10. Slave Relays
11. Schedules
12. BACnet
13. Exit & Save
Enter Menu Selection >
9 - Slave Inputs
This menu provides a means to configure any slave
unit input through the configuration port of the
master unit. Slave inputs are modified one channel
at a time. After modification, the changes must be
downloaded to the slave unit in order for the changes
to take effect. The data fields and parameters
are identical to the analog/digital inputs described
earlier in this manual. The example below shows
how the slave units are accessed.
Enter Menu Selection >9
Unit2: comproom4
Unit3: NA
Unit4: NA
Unit5: NA
Slave confi guration: Enter slave
number (2-5) >2
Slave Unit: comproom4
Gathering data from unit .. done
Input Configuration Menu
Channel #A1 of 20
Current Readings: Raw = 0.000 mA Calc
= 22
1. Type: 4-20
2. Gain: 25
3. Offset: 22
4. High Limit 2: 200
5. High Limit 1: 100
6. Low Limit 1: -2147483647
7. Low Limit 2: -2147483647
8. Relay Cntrl; 1
9. Unit of Measure: Deg C
10. Label: Temp. in Room
11. Alarm Delay: 0 (Secs)
12. Hysteresis: 0
13. Alarm Dial Out: 0,0,0,0,0
14. BACnet Instance:
15. BACnet Units:
18. Email Recipients:
19. Alarm Disable Sch: None
20. Previous Channel
21. Next Channel
22. Return
DL. Download Changes to Module
Enter Menu Selection >