RLE FMS8 User Manual
Page 30
Falcon User Guide
30
Falcon Links
The Falcon Links link allows up to four
Falcons or IP addressable devices to link to the
Falcon.
Modem
The Modem link allows users to configure the
Falcon’s internal modem. The initialization string
can be a maximum of 38 characters.
&c1
and
&d3
are mandatory.
s0=1
sets the modem to answer
after one ring.
The dial prefix should be a specific Hayes
compatible command or dial modifier. It is also
limited to 38 characters. The default is set to
atdt
.
Pager Deliveries
designates the number
of times to call the pager until the alarm is
acknowledged - 1 to 255. Pagers are called in
sequence. For example, if
Pager Deliveries
is
set to 3 and pagers 1, 7, and 10 are programmed to
be notified, the Falcon dials 1, 7, 10, 1, 7, 10, 1,
7, 10. As soon as the alarm is acknowledged, the
Falcon quits dialing the pagers with that particular
access code. Pagers with different access codes are
still dialed.
Pager Interval
allots the number of minutes to
wait between redials.
Pager No Ack Alarm
establishes a number to
call if the alarm isn’t acknowledged. A numbered
contact (one through 16) designates the number to
call.
Pager Baud Rate
designates the pager baud rate.
Pager Unsuccessful Traps
will allow the
Falcon to send an SNMP trap to the NMS if set to
YES
.
Pager Resend
will send all unacknowledged
alarms in the Alarm History menu if set to
YES.
It will only send the last unacknowledged alarm if
set at
NO.
Modem Password
defines a remote access
password, seven characters max.
Redial Attempts
sets a number of times to call a
number until the call is successful, from one to 255.
Redial Interval
establishes the number of
minutes to wait between redials, from one to 255.
Comm Check Phone
defines a numbered contact
(one through 16) to call to check communications.
Comm Check Time
sets a time (24 hour format) to
make the communications check.
Force Alarm Acknowledge Code
acknowledges
all unacknowledged alarms. This acts as a master
code and can override all other alarm acknowledge
codes.
Changes will not go into effect until the
Submit
Changes
button is clicked.